Water System Design Parameters
The following are a
list of design parameters that are important in the design of gravity-flow
water systems :
- Maximum Pressure Limits : The taps and valves
closed state, should be the maximum pressure condition for the
system. Maximum head limits for the pipe work will be used to
carry out the calculations. This scenario is used at the start
of the design to be able to place any break-pressure tanks that
may be required.
- Safe Yield : The safe yield is the minimum
flow from the water source. It is important to not draw more than
this supply from the system at any point. If this happens then
spring boxes and/or break pressure tanks will run dry and air
will enter the system.
- Negative or Low Pressure Head : If the pressure
head (P in the Bernoulli Equation) becomes negative at any point
in the system then two things may happen. Firstly a siphon effect
is occurring which is trying to suck water into the system. This
is undesirable as polluted groundwater may be introduced into
the system. Secondly, large negative pressures can cause air to
come out of solution in the water and cause air-blocks. Jordan
[P.52] suggests that the pressure head should, if possible, not
fall below 10m (98100 Pa pressure) anywhere in the system and
never go negative.
- Velocity Limits : The flow velocity in the
pipelines should not be to great as particles suspended in the
water will cause excessive erosion. Also if the velocity is too
low then these particles will settle out of the flow and may clog
the pipes at low points. This then requires washouts at low points
in the system. Jordan [P.53] suggests that the minimum velocity
should be 0.7m/s and the maximum 3.0m/s.
- Natural Flow : Natural Flow (see Section
8 i)) may be allowed to occur in the system at some sections of
pipe. Natural flow can be problematic in that the water velocity
may exceed the limits set in parameter 4 above and/or increase
the flow rate above the safe yield parameter 2. Close attention
should be made to these situations.
- Residual Head : The residual head at
a tap stand or valve is important. If it's too high it will cause
erosion of the valve and if it is too low then the flow will be
minimal. Jordan [P.141] suggests the following limits :
- Absolute minimum : 7m
- Low end of desired range : 10m
- Most desirable : 15m
- High end of desired range : 30m
- Absolute maximum : 56m
- Air-blocks : These occur when there
are topographic features between the source and the collecting
tank that are lower than the collecting tank. Energy is lost from
the system as these air-blocks are compressed and can result in
no flow. Jordan [P.55] gives the following design practices to
avoid air-blocks :
- Arrange pipe sizes to minimise the frictional
head loss between the source and the first air-block.
- Use larger-sized pipe at the top and
smaller sized pipe at the bottom of the critical sections
where air is going to be trapped.
- The higher air blocks are the more critical
ones and should be eliminated or minimised first.
- Air valves can be designed into the system
to allow trapped air to escape.
- Cost : Wherever possible smaller pipe diameters
should be used, as they are cheaper. Combinations of pipes can
often produce cheaper solutions than using just one pipe size.
However pipe lengths should be rounded to the nearest 100m length.
Also the number of concrete structures such as break-pressure
tanks should be minimised.
Large systems (say, 100 taps or more) are difficult
to analyse mathematically and meeting some of the above parameters
in a case where all of the taps open may lead to an over design
of the system. In such cases an acceptable rule of thumb is to allow
a flow rate of 0.02 litres per second when all of the taps are open.